GLC SeriesGLC Series
GLC - “Gaseous Liquid Cooled” generators are Baldors response to an increasing demand for larger gaseous powered Gen sets. Baldor’s GLC generators are a custom product offering whereby the generators are configured to a customers set of specifications.  The current GLC product runs from 30 kW - 100 kW. General Motors engines are being used on all the gaseous units. The six generator sets described here use either LP Gas or Natural Gas.  There is a wide selection of accessories and options available.

 

 

Model #

Rating
Standby Power

Voltage

Phase

Frequency

Engine Model and Type

Cylinders

RPM

Fuel Consump. at Full Load

GLC30

30 kW LP
30 kW NG

120 / 208

3

60 Hz

General Motors, Vortec, 4 cycle, Natural Aspiration

V-6

1800

4.2 cfh LP
12.4 cfh NG

GLC35

35 kW LP
35 kW NG

120 / 208

3

60 Hz

General Motors, Vortec, 4 cycle, Natural Aspiration

V-6

1800

4.7 cfh LP
13.9 cfh NG

GLC45

44 kW LP
39 kW NG

120 / 208

3

60 Hz

General Motors, Vortec, 4 cycle, Natural Aspiration

V-6

1800

6.9 cfh LP
16.5 cfh NG

GLC50

50 kW LP
50 kW NG

120 / 208

3

60 Hz

General Motors, Vortec, 4 cycle, Natural Aspiration

V-8

1800

8.0 cfh LP
19.96 cfh NG

GLC80

80 kW LP
80 kW NG

120 / 208

3

60 Hz

General Motors, Vortec, 4 cycle, Natural Aspiration

V-8

1800

12 cfh LP
28.7 cfh NG

GLC100

99 kW LP
86 kW NG

120 / 208

3

60 Hz

General Motors, Vortec, 4 cycle, Natural Aspiration

V-8

1800

12 cfh LP
28.7 cfh NG

 

 

Controls
 

 

Standard Features:

  • Timers - Engine start, Cooldown, Oil Bypass, Cycle crank
  • Control Switches - Run/Auto/Load test, Horn test, Lamp test, Common
  • LCD Display Menu - AC metering, Timer, Alarm/Shutdown, Engine
  • Diagnostic LED indicators - Watchdog (CPU Running), run output energized, remote start signal initiated, common fail output energized
  • Fully configurable from front panel keypad
  • Password protected
  • Low Oil Pressure Alarm Light
  • High coolant Temperature Alarm Light
  • Overspeed Alarm Light

Controller:

  • Microprocessor-based circuitry
  • Standard features meet requirements of NFPA110 Level 1
  • Backlit LCD display
  • Digital 3-phase voltage, current & frequency metering
  • Up to 28 alarm/shutdown fault circuits analog/digital inputs
  • EMI/RFI noise immunity per IEEE C62.41
  • Certified to UL #508

Shutdowns:

  • Overspeed
  • Over-crank
  • Loss of speed signal
  • High engine temperature
  • Low Oil Pressure Shutdown
  • Emergency Stop

 

 

Accessories & Options
 

 

Control Panel:

  • High Coolant Temp. Pre-alarm
  • Low Oil Pressure Pre-alarm
  • Alarm Horn with Switch
  • Remote Stop-Start
  • Remote Annunciator
  • Run Relay
  • Dry Contacts

Engine Electrical System:

  • 12 or 24 Volt Operation
  • Batteries
  • Battery Rack
  • Battery Cables
  • Battery Charger - Automatic
  • Battery Charger - Trickle

Engine Fuel System:

  • Flexible Fuel Lines

Engine Exhaust System:

  • Industrial Silencer
  • Residential Silencer Exhaust Flex
  • Rain Cap

General Accessories:

  • Main Line Circuit Breaker
  • Shunt Trip
  • Alternator Heater
  • Field Circuit Breaker
  • PMG

Miscellaneous:

  • Weather Protective Enclosure
  • Sound Attenuated Enclosure
  • Vibration Isolators
  • Coolant Heater